§ 8-1-901. Chapter 3, Building Planning, amended.  


Latest version.
  • Chapter 3 Building Planning is adopted in its entirety with the following amendments and additions:

    SECTION R301.2 Climatic and Geographic Design Criteria is amended as follows:

    R301.2 Climatic and Geographic Design Criteria, Table R301.2(1) Climatic and Geographic Design Criteria.

    TABLE R301.2(1)
    CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA

    Ground Snow Load Wind Design Seismic Design Category f Subject To Damage From Winter Design Temp e Ice
    Barrier Under-
    layment Required h
    Flood Hazards g Air Freezing Index i Mean Annual Temp j
    Speed d (mph) Topo-
    graphic Effects k
    Weather-
    ing a
    Frost Line Depth b Termite c
    Zero 85 No D 2 or E Negligible 12—24" Very Heavy 43 No See Exhibit B 0 60

     

    For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s.

    a  Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column shall be filled in with the weathering index (i.e., "negligible," "moderate" or "severe") for concrete as determined from the Weathering Probability Map [Figure R301.2(3)]. The grade of masonry units shall be determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652.

    b  The frost line depth may require deeper footings than indicated in Figure R403.1 (1). The jurisdiction shall fill in the frost line depth column with the minimum depth of footing below finish grade.

    c  The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a history of local subterranean termite damage.

    d  The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [Figure R30l.2(4)].Wind exposure category shall be determined on a site-specific basis in accordance with Section R301.2.1.4.

    e  Temperatures shall be permitted to reflect local climates or local weather experience as determined by the Building Official.

    f  The jurisdiction shall fill in this part of the table with the seismic design category determined from Section R301.2.2.1.

    g  The jurisdiction shall fill in this part of the table with (a) the date of the jurisdiction's entry into the National Flood Insurance Program (date of adoption of the first code or ordinance for management of flood hazard areas), (b) the date(s) of the Flood Insurance Study and (c) the panel numbers and dates of all currently effective FIRMs and FBFMs or other flood hazard map adopted by the authority having jurisdiction, as amended.

    h  In accordance with Sections R905.2.7.1, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1, where there has been a history of local damage from the effects of ice damming, the jurisdiction shall fill in this part of the table with "YES." Otherwise, the jurisdiction shall fill in this part of the table with "NO."

    i  The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (BF-days) from Figure R403.3(2) or from the 100-year (99%) value on the National Climatic Data Center data table "Air Freezing Index- USA Method (Base 32°)" at www.ncdc.noaa.gov/fpsf.htrnl.

    j  The jurisdiction shall fill in this part of the table with the mean annual temperature from the National Climatic Data Center data table "Air Freezing Index-USA Method (Base 32°F)" at www.ncdc.noaa.gov/fpsf.html .

    k  In accordance with Section R301.2.1.5, where there is local historical data documenting structural damage to buildings due to topographic wind speed-up effects, the jurisdiction shall fill in this part of the table with "YES." Otherwise, the jurisdiction shall indicate "NO" in this part of the table.

    _____

    SECTION R301.9 Fuel Modification Requirements for New Construction is hereby added as follows:

    R301.9 Fuel Modification Requirements for New Construction. All new structures and facilities adjoining land containing hazardous combustible vegetation shall be approved and in accordance with the requirements of OCFA Guideline C-05 "Vegetation Management Guideline — Technical Design for new Construction Fuel Modification Plans and Maintenance Program."

    SECTION R309.6 Fire sprinkler attached garages, and carports with habitable space above is hereby amended by modifying the exception to read as follows:

    Exception: An automatic residential fire sprinkler system shall not be required when additions or alterations are made to existing carports and/or garages that do not have an automatic fire sprinkler system installed unless a sprinkler system is required in accordance with California Fire Code Section 903.2.8.

    SECTION R313.1 Townhouse automatic fire sprinkler systems is hereby amended by modifying the exception to read as follows:

    Exception: An automatic residential fire sprinkler system shall not be required when additions or alterations are made to existing townhouses that do not have an automatic fire sprinkler system installed unless a sprinkler system is required in accordance with California Fire Code Section 903.2.8.

    SECTION R313.2 One- and two-family dwellings automatic fire sprinkler systems is hereby amended by modifying the exception to read as follows:

    Exception: An automatic residential fire sprinkler system shall not be required for additions or alterations to existing buildings that are not already provided with an automatic sprinkler system unless a sprinkler system is required in accordance with California Fire Code Section 903.2.8.

    SECTION R313.3.6.2.2 Calculation procedure is hereby amended to read as follows:

    SECTION R313.3.6.2.2 Calculation procedure. Determination of the required size for water distribution piping shall be in accordance with the following procedure and California Fire Code Section 903.3.5.3.

    Section R319.1 Address identification is hereby amended to read as follows:

    R319 Site Address. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches in height with a stroke width of not less than 0.5 inch. Where required by the Fire Code Official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained.

    SECTION R337.1.3 Application is hereby amended to read as follows:

    R337.1.3 Application. New buildings located in any Fire Hazard Severity Zone or any Wildland-Urban Interface Fire Area designated by the enforcing agency constructed after the application date, and additions to and remodel of buildings constructed before 2012 located in areas currently designated as such, shall comply with the provisions of this chapter. The provisions shall also apply to additions, remodels, and accessory structures located within 100 feet of a fuel modification zone, vegetation management area, or similar area containing hazardous combustible vegetation, regardless of whether the property is currently located in a designated Fire Hazard Severity Zone or Wildland-Urban Interface Area, when materials and/or construction methods for exterior wildfire exposure were previously required at the property by the Building or Fire Code Official.

    Exceptions:

    1.

    Buildings of an accessory character classified as a Group U occupancy and not exceeding 120 square feet in floor area, when located at least 30 feet from an applicable building.

    2.

    Buildings of an accessory character classified as a Group U occupancy of any size located at least 50 feet from an applicable building.

    3.

    Buildings classified as a Group U Agricultural Building, as defined in Section 202 of this code (see also Appendix C - Group U Agricultural Buildings), when located at least 50 feet from an applicable building.

    SECTION R337.1.6 Fuel Modification Requirements for New Construction is hereby added as follows:

    R337.1.6 Fuel Modification Requirements for New Construction. All new buildings to be built or installed in a wildfire risk area shall comply with the following:

    1.

    Preliminary fuel modification plans shall be submitted to and approved by the Fire Code Official prior to or concurrently with the approval of any tentative map.

    2.

    Final fuel modification plans shall be submitted to and approved by the Fire Code Official prior to the issuance of a grading permit.

    3.

    The fuel modification plans shall meet the criteria set forth in the Fuel Modification Section of OCFA Guideline C-05 "Vegetation Management Guideline - Technical Design for New Construction Fuel Modification Plans and Maintenance Program."

    3.1.

    The fuel modification plan shall include provisions for the maintenance of the fuel modification in perpetuity.

    4.

    The fuel modification plan may be altered if conditions change. Any alterations to the fuel modification areas shall have prior approval from the Fire Code Official.

    5.

    All elements of the fuel modification plan shall be maintained in accordance with the approved plan and are subject to the enforcement process outlined in the Fire Code.

(Ord. No. 2016-185, § 3, 12-6-16)